A load impedance absorbing 4 W with a leading power factor of 0.80 operating at radial frequency of W=60 rad/sec. Assuming that the RMS current that the impedance draws from the source is 1 A, then determine the value, and type, of the element (by using the suitable unit in the provided field below)) that is needed to be connected in parallel to this impedance in order to correct its power factor to a value of 0.90 lagging. • Use 6 decimal places for the value • Select one of the following letters (or group of letters), for the units: A,V, W, VAR, VA, F, H, Ohms. Your choice of the unit will show your correct understanding of the element needed to correct the power factor.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter2: Fundamentals
Section: Chapter Questions
Problem 2.3P: The instantaneous voltage across a circuit element is v(t)=400sin(t+30)volts, and the instantaneous...
icon
Related questions
Question
A load impedance absorbing 4 W with a leading power factor of 0.80 operating at
radial frequency of W = 60 rad/sec. Assuming that the RMS current that the
impedance draws from the source is 1 A, then determine the value, and type, of the
element (by using the suitable unit in the provided field below)) that is needed to be
connected in parallel to this impedance in order to correct its power factor to a value
of 0.90 lagging.
• Use 6 decimal places for the value
Select one of the following letters (or group of letters), for the units: A,V, W,
VAR, VA, F, H, Ohms. Your choice of the unit will show your correct
understanding of the element needed to correct the power factor.
Transcribed Image Text:A load impedance absorbing 4 W with a leading power factor of 0.80 operating at radial frequency of W = 60 rad/sec. Assuming that the RMS current that the impedance draws from the source is 1 A, then determine the value, and type, of the element (by using the suitable unit in the provided field below)) that is needed to be connected in parallel to this impedance in order to correct its power factor to a value of 0.90 lagging. • Use 6 decimal places for the value Select one of the following letters (or group of letters), for the units: A,V, W, VAR, VA, F, H, Ohms. Your choice of the unit will show your correct understanding of the element needed to correct the power factor.
Expert Solution
steps

Step by step

Solved in 3 steps

Blurred answer
Knowledge Booster
Analysis of Single Phase and Three Phase System
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning