A 25 MVA, 13.2 kV alternator with solidly grounded neutral has a subtransient reactance of 0.40 p.u. The negative and zero sequence reactances are 0.20 and 0.3 p.u. respectively. Find the fault current when,   (i) A single line to ground fault occurs at the terminals of an unloaded alternator and (ii) ALL fault occurs.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.35P: Consider a bank of this single-phase two-winding transformers whose high-voltage terminals are...
icon
Related questions
icon
Concept explainers
Question

A 25 MVA, 13.2 kV alternator with solidly grounded neutral has a subtransient reactance of 0.40 p.u. The negative and zero sequence reactances are 0.20 and 0.3 p.u. respectively. Find the fault current when,

 

(i) A single line to ground fault occurs at the terminals of an unloaded alternator and (ii) ALL fault occurs.

Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 3 steps with 3 images

Blurred answer
Knowledge Booster
Fault analysis
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning