A 3-phase star connected alternator is rated 30 MVA, 13.8 kV and has the following sequence values X1 = 0.25 p.u. X2= 0.35 p.u. and Xo = 0.10 p.u.The neutral of the alternator is solidly grounded. Determine the sequence components of currents and fault current when double line to ground (LLG) occurs on its teminals. Assume that the alternator is unloaded and is operating at rated voltage. o la1 = -j3.052; Ia2 = -j0.677; Iao = -j2.37, If = -j7.11 or 7.11 L-900 o la1 = -j1.052; Ia2 = -j0.477; Iao = -j5.37, If = -j3.11 or 3.11 L-900 %3D None of these o Ia1 = -j5.052; Ia2 = -j0.577; Iao = -j3.37, If = -j9.11 or 9.11 L-900 %3D

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.56P: Three single-phase two-winding transformers, each rated 3kVA,220/110volts,60Hz, with a 0.10 per-unit...
icon
Related questions
Question
A 3-phase star connected alternator is rated 30 MVA, 13.8 kV and has the following sequence
values X1 = 0.25 p.u. X2 = 0.35 p.u. and Xo = 0.10 p.u.The neutral of the alternator is solidly
grounded. Determine the sequence components of currents and fault current when double line to
ground (LLG) occurs on its terminals. Assume that the alternator is unloaded and is operating at
rated voltage.
o la1 = -j3.052; Ia2 = -j0.677; Iao = -j2.37, If = -j7.11 or 7.11 L-900
o la1 = -j1.052; Ia2 = -j0.477; Iao = -j5.37, If = -j3.11 or 3.11 L-900
None of these
o la1 = -j5.052; Ia2 = -j0.577; Iao = -j3.37, If = -j9.11 or 9.11 L-900
%3D
%3D
Transcribed Image Text:A 3-phase star connected alternator is rated 30 MVA, 13.8 kV and has the following sequence values X1 = 0.25 p.u. X2 = 0.35 p.u. and Xo = 0.10 p.u.The neutral of the alternator is solidly grounded. Determine the sequence components of currents and fault current when double line to ground (LLG) occurs on its terminals. Assume that the alternator is unloaded and is operating at rated voltage. o la1 = -j3.052; Ia2 = -j0.677; Iao = -j2.37, If = -j7.11 or 7.11 L-900 o la1 = -j1.052; Ia2 = -j0.477; Iao = -j5.37, If = -j3.11 or 3.11 L-900 None of these o la1 = -j5.052; Ia2 = -j0.577; Iao = -j3.37, If = -j9.11 or 9.11 L-900 %3D %3D
Expert Solution
steps

Step by step

Solved in 2 steps with 1 images

Blurred answer
Knowledge Booster
Three Phase Transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning