Table 10.5 Drainage and Water Fixture Unit Values and Minimum Pressure and Pipe Size Requirements Drainage Fixture Public or General Water closet, flushometer Water closet, gravity tank Water closet, pressure tank Urinal, flushometer Urinal, tank Lavatory Bathtub Shower Service sink Kitchen sink Electric water cooler Load Value, dfu 6 4 2 4 2 1 2 2 3 3 0.5 Minimum Pipe Diameter 4 3⁰ 3⁰ 2-3 2 2 2 2 3 2 2 Water Load Values, wsfu Cold 10 5 2 5 3 1.5 3 3 2.25 3 0.25 Hot 1.5 3 3 2.25 3 Total 10 5 2 5 3 2 4 4 3 4 0.25 Minimum at Fixture psig 20-25 8-10 25-30 15-20 8-10 8-10 8-10 8-10 8-10 8-10 8-10 Pipe Diameter 1 1/2 ¹1/2 3/4 ¹/2 3/8 ¹2 3/4 3/4 3/4 3/8

Solid Waste Engineering
3rd Edition
ISBN:9781305635203
Author:Worrell, William A.
Publisher:Worrell, William A.
Chapter8: Landfills
Section: Chapter Questions
Problem 8.9P
icon
Related questions
Question

The following fixtures will be needed for a 1,200 seat movie theater:

  • Flushometer Water Closets: 3 Men's, 8 women's
  • Flushometer Urinals: 3 men's
  • Lavatories: 3 Men's, 5 Women's
  • Electric Water Coolers: 6 total
  • Service Sinks: 1 total

Find the total drainage fixture units (DFUs) for this movie theater.

Table 10.5 Drainage and Water Fixture Unit Values and Minimum Pressure and Pipe Size Requirements
Drainage
Fixture
Public or General
Water closet, flushometer
Water closet, gravity tank
Water closet, pressure tank
Urinal, flushometer
Urinal, tank
Lavatory
Bathtub
Shower
Service sink
Kitchen sink
Electric water cooler
Load Value, dfu
6
4
2
4
2
1
2
2
3
3
0.5
Minimum Pipe Diameter
4
3⁰
3⁰
2-3
2
2
2
2
3
2
2
Water
Load Values, wsfu
Cold
10
5
2
5
3
1.5
3
3
2.25
3
0.25
Hot
1.5
3
3
2.25
3
Total
10
5
2
5
3
2
4
4
3
4
0.25
Minimum at Fixture
psig
20-25
8-10
25-30
15-20
8-10
8-10
8-10
8-10
8-10
8-10
8-10
Pipe Diameter
1
1/2
¹1/2
3/4
¹/2
3/8
¹2
3/4
3/4
3/4
3/8
Transcribed Image Text:Table 10.5 Drainage and Water Fixture Unit Values and Minimum Pressure and Pipe Size Requirements Drainage Fixture Public or General Water closet, flushometer Water closet, gravity tank Water closet, pressure tank Urinal, flushometer Urinal, tank Lavatory Bathtub Shower Service sink Kitchen sink Electric water cooler Load Value, dfu 6 4 2 4 2 1 2 2 3 3 0.5 Minimum Pipe Diameter 4 3⁰ 3⁰ 2-3 2 2 2 2 3 2 2 Water Load Values, wsfu Cold 10 5 2 5 3 1.5 3 3 2.25 3 0.25 Hot 1.5 3 3 2.25 3 Total 10 5 2 5 3 2 4 4 3 4 0.25 Minimum at Fixture psig 20-25 8-10 25-30 15-20 8-10 8-10 8-10 8-10 8-10 8-10 8-10 Pipe Diameter 1 1/2 ¹1/2 3/4 ¹/2 3/8 ¹2 3/4 3/4 3/4 3/8
AI-Generated Solution
AI-generated content may present inaccurate or offensive content that does not represent bartleby’s views.
steps

Unlock instant AI solutions

Tap the button
to generate a solution

Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Solid Waste Engineering
Solid Waste Engineering
Civil Engineering
ISBN:
9781305635203
Author:
Worrell, William A.
Publisher:
Cengage Learning,