A three-phase, 7.5Hp, 230V, 60Hz, Delta connected induction motor was tested and give the following input data: No load Test: I = 10A P = 650W slip = 0.8333% Load Test: I = 19A, P = 6800W slip = 3% Resistance test between two stator terminals: Vdc = 9V , Idc = 20A Assume K = 1.5 Determine the efficiency of the motor during the load test

Delmar's Standard Textbook Of Electricity
7th Edition
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Stephen L. Herman
Chapter32: Three-phase Motors
Section: Chapter Questions
Problem 6RQ: Name three factors that determine the torque produced by an induction motor.
icon
Related questions
Question

A three-phase, 7.5Hp, 230V, 60Hz, Delta connected induction motor was tested and give the following input data:

No load Test: I = 10A P = 650W slip = 0.8333%

Load Test: I = 19A, P = 6800W slip = 3%

Resistance test between two stator terminals: Vdc = 9V , Idc = 20A

Assume K = 1.5

Determine the efficiency of the motor during the load test

Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 3 steps

Blurred answer
Knowledge Booster
Three phase Induction Motor
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning