A factory has an electrical load of 800 kW at a lag- ging power factor of 0.6. An additional variable power factor load is to be added to the factory. The new load will add 160 kW to the real power load of the factory. The power factor of the added load is to be adjusted so that the overall power factor of the factory is 0.96 lagging. a) Specify the reactive power associated with the added load. b) Does the added load absorb or deliver magne- tizing vars? c) What is the power factor of the additional load? d) Assume that the voltage at the input to the fac- tory is 1200 V (rms). What is the rms magnitude of the current into the factory before the vari- able power factor load is added? e) What is the rms magnitude of the current into the factory after the variable power factor load has been added?

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter2: Fundamentals
Section: Chapter Questions
Problem 2.7P: Let a 100V sinusoidal source be connected to a series combination of a 3 resistor, an 8 inductor,...
icon
Related questions
Question

Please show all steps, thank you

10.34 A factory has an electrical load of 800 kW at a lag-
ging power factor of 0.6. An additional variable
power factor load is to be added to the factory. The
new load will add 160 kW to the real power load of
the factory. The power factor of the added load is to
be adjusted so that the overall power factor of the
factory is 0.96 lagging.
a) Specify the reactive power associated with the
added load.
b) Does the added load absorb or deliver magne-
tizing vars?
c) What is the power factor of the additional load?
d) Assume that the voltage at the input to the fac-
tory is 1200 V (rms). What is the rms magnitude
of the current into the factory before the vari-
able power factor load is added?
What is the rms magnitude of the current into
the factory after the variable power factor load
has been added?
Transcribed Image Text:10.34 A factory has an electrical load of 800 kW at a lag- ging power factor of 0.6. An additional variable power factor load is to be added to the factory. The new load will add 160 kW to the real power load of the factory. The power factor of the added load is to be adjusted so that the overall power factor of the factory is 0.96 lagging. a) Specify the reactive power associated with the added load. b) Does the added load absorb or deliver magne- tizing vars? c) What is the power factor of the additional load? d) Assume that the voltage at the input to the fac- tory is 1200 V (rms). What is the rms magnitude of the current into the factory before the vari- able power factor load is added? What is the rms magnitude of the current into the factory after the variable power factor load has been added?
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 4 steps with 3 images

Blurred answer
Knowledge Booster
Source transformation method
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning