A commercial refrigerator with refrigerant-134a as the working fluid is used to keep the refrigerated space at -35°C by rejecting waste heat to cooling water that enters the condenser at 18°C at a rate of 0.35 kg/s and leaves at 26°C. The refrigerant enters the condenser at 1.2 MPa and 50°C and leaves at the same pressure subcooled by 5°C. The compressor consumes 3.3 kW of power. Use data from the tables. 26°C 1.2 MPa 5°C subcooled Expansion valve ↑ Condenser Water 18°C Evaporator PL 1.2 MPa 50°C Compressor Determine the minimum power input to the compressor for the same refrigeration load. The minimum power input to the compressor for the same refrigeration load is kW.

Refrigeration and Air Conditioning Technology (MindTap Course List)
8th Edition
ISBN:9781305578296
Author:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Chapter45: Domestic Refrigerators And Freezers
Section: Chapter Questions
Problem 12RQ: Refrigerators currently being manufactured in the United States are using______as their refrigerant.
icon
Related questions
Question
A commercial refrigerator with refrigerant-134a as the working fluid is used to keep the refrigerated space at -35°C by
rejecting waste heat to cooling water that enters the condenser at 18°C at a rate of 0.35 kg/s and leaves at 26°C. The
refrigerant enters the condenser at 1.2 MPa and 50°C and leaves at the same pressure subcooled by 5°C. The compressor
consumes 3.3 kW of power. Use data from the tables.
26°C
1.2 MPa
5°C subcooled
Expansion
valve
Condenser
Evaporator
ė
Water
18°C
1.2 MPa
50°C
Compressor
in
Determine the minimum power input to the compressor for the same refrigeration load.
The minimum power input to the compressor for the same refrigeration load is
KW.
K
Transcribed Image Text:A commercial refrigerator with refrigerant-134a as the working fluid is used to keep the refrigerated space at -35°C by rejecting waste heat to cooling water that enters the condenser at 18°C at a rate of 0.35 kg/s and leaves at 26°C. The refrigerant enters the condenser at 1.2 MPa and 50°C and leaves at the same pressure subcooled by 5°C. The compressor consumes 3.3 kW of power. Use data from the tables. 26°C 1.2 MPa 5°C subcooled Expansion valve Condenser Evaporator ė Water 18°C 1.2 MPa 50°C Compressor in Determine the minimum power input to the compressor for the same refrigeration load. The minimum power input to the compressor for the same refrigeration load is KW. K
Expert Solution
steps

Step by step

Solved in 3 steps with 3 images

Blurred answer
Knowledge Booster
Refrigeration and Air Conditioning
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Refrigeration and Air Conditioning Technology (Mi…
Refrigeration and Air Conditioning Technology (Mi…
Mechanical Engineering
ISBN:
9781305578296
Author:
John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:
Cengage Learning