A commercial refrigerator with refrigerant-134a as the working fluid is used to keep the refrigerated space at -35°C by rejecting waste heat to cooling water that enters the condenser at 18°C at a rate of 0.35 kg/s and leaves at 26°C. The refrigerant enters the condenser at 1.2 MPa and 50°C and leaves at the same pressure subcooled by 5°C. The compressor consumes 3.3 kW of power. Use data from the tables.

Refrigeration and Air Conditioning Technology (MindTap Course List)
8th Edition
ISBN:9781305578296
Author:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Chapter28: Special Refrigeration Applications
Section: Chapter Questions
Problem 15RQ: Why is two-stage compression popular for extra-low-temperature refrigeration systems?
icon
Related questions
Question
es
A commercial refrigerator with refrigerant-134a as the working fluid is used to keep the refrigerated space at -35°C by
rejecting waste heat to cooling water that enters the condenser at 18°C at a rate of 0.35 kg/s and leaves at 26°C. The
refrigerant enters the condenser at 1.2 MPa and 50°C and leaves at the same pressure subcooled by 5°C. The compressor
consumes 3.3 kW of power. Use data from the tables.
26°C
1.2 MPa
50 subcooled
fo
Expansion
valve
Condenser
Evaporator
000
QL
Water
18°C
1.2 MPa
50°C
Compressor
kW.
W
in
Determine the refrigeration load.
The refrigeration load is
(You must provide an answer before moving to the next part.)
27
Transcribed Image Text:es A commercial refrigerator with refrigerant-134a as the working fluid is used to keep the refrigerated space at -35°C by rejecting waste heat to cooling water that enters the condenser at 18°C at a rate of 0.35 kg/s and leaves at 26°C. The refrigerant enters the condenser at 1.2 MPa and 50°C and leaves at the same pressure subcooled by 5°C. The compressor consumes 3.3 kW of power. Use data from the tables. 26°C 1.2 MPa 50 subcooled fo Expansion valve Condenser Evaporator 000 QL Water 18°C 1.2 MPa 50°C Compressor kW. W in Determine the refrigeration load. The refrigeration load is (You must provide an answer before moving to the next part.) 27
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps with 1 images

Blurred answer
Knowledge Booster
Refrigeration and Air Conditioning
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Refrigeration and Air Conditioning Technology (Mi…
Refrigeration and Air Conditioning Technology (Mi…
Mechanical Engineering
ISBN:
9781305578296
Author:
John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:
Cengage Learning