The maximum size overcurrent device for primary only protection of a three-phase 45 kVA transformer with a 480V primary and a 120/208V secondary is

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.21MCQ: In order to avoid difficulties with third-harmonic exciting current, which three-phase transformer...
icon
Related questions
Question
The maximum size overcurrent device for primary only protection of a three-phase 45 kVA transformer with a 480V primary and a 120/208V
secondary is
O
a. 50A
Ob.60A
Oc. 70A
Od.90A
Transcribed Image Text:The maximum size overcurrent device for primary only protection of a three-phase 45 kVA transformer with a 480V primary and a 120/208V secondary is O a. 50A Ob.60A Oc. 70A Od.90A
Expert Solution
Step 1 Definition

Transformer is a static device which transfers power from one circuit to another circuit without change in frequency.

As transformer does not change the frequency of the system, it can be treated as constant frequency device.

As transformer transfers almost same amount of power from one circuit to another circuit, it can be treated as constant power device.

trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps

Blurred answer
Knowledge Booster
Single phase transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning