The following data were obtained on a 50 kVA 2400/120 V transformer : Open circuit test, instruments on low voltage side: Waltmeter reading = 396 Watts Ammeter reading = 9.65 amperes Voltmeter reading = 120 Volts Short circuit test, instruments on high voltage side: Waltmeter reading = 810 Watts Ammeter reading = 20.8 amperes Voltmeter reading = 92 Volts Find the efficiency when rated kVA is delivered to a load having a power factor of 0.8 lagging. The following data were obtained on a 50 kVA 2400/120 V transformer:

Electrical Transformers and Rotating Machines
4th Edition
ISBN:9781305494817
Author:Stephen L. Herman
Publisher:Stephen L. Herman
Chapter10: Transformer Installation
Section: Chapter Questions
Problem 6RQ: A 10 kVA transformer has a primary voltage rating of 240 volts and a secondary voltage rating of 480...
icon
Related questions
Question
The following data were obtained on a 50 kVA 2400/120 V transformer:
Open circuit test, instruments on low voltage side:
Waltmeter reading = 396 Watts
Ammeter reading = 9.65 amperes
Voltmeter reading = 120 Volts
Short circuit test, instruments on high voltage side:
Waltmeter reading = 810 Watts
Ammeter reading = 20.8 amperes
Voltmeter reading = 92 Volts
Find the efficiency when rated kVA is delivered to a load having a power
factor of 0.8 lagging.The following data were obtained on a 50 kVA 2400/120 V transformer :
Open circuit test, instruments on low voltage side:
Waltmeter reading = 396 Watts
Ammeter reading = 9.65 amperes
Voltmeter reading = 120 Volts
Short circuit test, instruments on high voltage side:
Waltmeter reading = 810 Watts
Ammeter reading = 20.8 amperes
Voltmeter reading = 92 Volts
Find the efficiency when rated kVA is delivered to a load having a power
factor of 0.8 lagging.
Transcribed Image Text:The following data were obtained on a 50 kVA 2400/120 V transformer: Open circuit test, instruments on low voltage side: Waltmeter reading = 396 Watts Ammeter reading = 9.65 amperes Voltmeter reading = 120 Volts Short circuit test, instruments on high voltage side: Waltmeter reading = 810 Watts Ammeter reading = 20.8 amperes Voltmeter reading = 92 Volts Find the efficiency when rated kVA is delivered to a load having a power factor of 0.8 lagging.The following data were obtained on a 50 kVA 2400/120 V transformer : Open circuit test, instruments on low voltage side: Waltmeter reading = 396 Watts Ammeter reading = 9.65 amperes Voltmeter reading = 120 Volts Short circuit test, instruments on high voltage side: Waltmeter reading = 810 Watts Ammeter reading = 20.8 amperes Voltmeter reading = 92 Volts Find the efficiency when rated kVA is delivered to a load having a power factor of 0.8 lagging.
Expert Solution
steps

Step by step

Solved in 2 steps with 1 images

Blurred answer
Knowledge Booster
Conduction
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Electrical Transformers and Rotating Machines
Electrical Transformers and Rotating Machines
Mechanical Engineering
ISBN:
9781305494817
Author:
Stephen L. Herman
Publisher:
Cengage Learning