Part B - Calculating apparent power and power factor A load operates at a voltage of V₂ = 100 V-rms and absorbs P = 70 W and Q=37 VAR of power. Use this information to calculate the apparent power (S) and the power factor (pf) load Enter comma separated numerical answers with three significant figures. ▸ View Available Hint(s) S, pf = Submit VAX Ivec Part C - Calculating load impedance Z= A load absorbs 45403 W at a lagging power factor of pf = 0.57. If the current flowing through the load is i, = 0.001 A-rms, determine the impedance of the load Enter a complex number with three significant figures. ▸ View Available Hint(s) VAX vec ? ? VA, no unit 52

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter2: Fundamentals
Section: Chapter Questions
Problem 2.7P: Let a 100V sinusoidal source be connected to a series combination of a 3 resistor, an 8 inductor,...
icon
Related questions
Question

Parts B and C.

Learning Goal:
To use information about the power provided by a source or absorbed by a load
to calculate average power, reactive power, apparent power, and the power
factor.
Before completing this tutorial, make sure you are familiar with the relationships
between average, reactive, and apparent power and the power factor.
Part A - Calculating average power, reactive power, and the power factor
A load absorbs S = 18 kVA at a leading power factor of pf = 0.90. Use this information to calculate the average (P) and reactive (Q) power for the load.
Enter comma separated numerical answers with three significant figures.
► View Available Hint(s)
P, Q = 16.2,-7.85 kW, KVAR
Submit
Correct
Term 2: Correct answer is shown. Your answer -7.846 kW, kVAR was either rounded differently or used a different number of significant figures than required for this part.
Keep in mind that the power triangle requires that the average and reactive powers be numerically smaller in value than the apparent power
Part B - Calculating apparent power and power factor
A load operates at a voltage of V₂ = 100 V-rms and absorbs P = 70 W and Q = 37 VAR of power. Use this information to calculate the apparent power (S) and the power factor (pf) for the
load.
Enter comma separated numerical answers with three significant figures.
► View Available Hint(s)
S, pf =
Previous Answers
Submit
Z =
VG | ΑΣΦ
Part C - Calculating load impedance
Submit
↓↑ vec
A load absorbs 45403 W at a lagging power factor of pf = 0.57. If the current flowing through the load is i = 0.001 A-rms, determine the impedance of the load.
Enter a complex number with three significant figures.
► View Available Hint(s)
ΞΑΣΦ
↓↑ vec
?
?
VA, no unit
Ω
Transcribed Image Text:Learning Goal: To use information about the power provided by a source or absorbed by a load to calculate average power, reactive power, apparent power, and the power factor. Before completing this tutorial, make sure you are familiar with the relationships between average, reactive, and apparent power and the power factor. Part A - Calculating average power, reactive power, and the power factor A load absorbs S = 18 kVA at a leading power factor of pf = 0.90. Use this information to calculate the average (P) and reactive (Q) power for the load. Enter comma separated numerical answers with three significant figures. ► View Available Hint(s) P, Q = 16.2,-7.85 kW, KVAR Submit Correct Term 2: Correct answer is shown. Your answer -7.846 kW, kVAR was either rounded differently or used a different number of significant figures than required for this part. Keep in mind that the power triangle requires that the average and reactive powers be numerically smaller in value than the apparent power Part B - Calculating apparent power and power factor A load operates at a voltage of V₂ = 100 V-rms and absorbs P = 70 W and Q = 37 VAR of power. Use this information to calculate the apparent power (S) and the power factor (pf) for the load. Enter comma separated numerical answers with three significant figures. ► View Available Hint(s) S, pf = Previous Answers Submit Z = VG | ΑΣΦ Part C - Calculating load impedance Submit ↓↑ vec A load absorbs 45403 W at a lagging power factor of pf = 0.57. If the current flowing through the load is i = 0.001 A-rms, determine the impedance of the load. Enter a complex number with three significant figures. ► View Available Hint(s) ΞΑΣΦ ↓↑ vec ? ? VA, no unit Ω
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 5 steps with 8 images

Blurred answer
Knowledge Booster
Inductor
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning