Home workl: A short-shunt compound generator delivers a load current of 30 A at 220 V, and has armature, series-field and shunt-fie resistances of 0.05 Q, 0.30 Q and 200 Q respectively. Calculate the induced e.m.f. and the armature current. Allow 1.0 V per brush for contact drop.
Home workl: A short-shunt compound generator delivers a load current of 30 A at 220 V, and has armature, series-field and shunt-fie resistances of 0.05 Q, 0.30 Q and 200 Q respectively. Calculate the induced e.m.f. and the armature current. Allow 1.0 V per brush for contact drop.
Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter12: Power System Controls
Section: Chapter Questions
Problem 12.4P
Related questions
Question
![Home workl: A short-shunt compound generator delivers a load
current of 30 A at 220 V, and has armature, series-field and shunt-field
resistances of 0.05 Q, 0.30 Q and 200 Q respectively. Calculate the
induced e.m.f. and the armature current. Allow 1.0 V per brush for
contact drop.
Home work2: A 4-pole, long-shunt lap-wound generator supplies 25
kW at a terminal voltage of 500 V. The armature resistance is 0.03 ohm,
series field resistance is 0.04 ohm and shunt field resistance is 200 ohm.
The brush drop may be taken as 1.0 V. Determine the e.m.f. generated.
Calculate also the No. of conductors if the speed is 1200 r.p.m. and flux
per pole is 0.02 weber. Neglect armature reaction.](/v2/_next/image?url=https%3A%2F%2Fcontent.bartleby.com%2Fqna-images%2Fquestion%2F8b30dffa-8d00-41b8-a140-7b43aa8f8b8b%2F71d1b221-3a08-45c9-b89a-13e0d6e2a15d%2Fw6hc3us_processed.jpeg&w=3840&q=75)
Transcribed Image Text:Home workl: A short-shunt compound generator delivers a load
current of 30 A at 220 V, and has armature, series-field and shunt-field
resistances of 0.05 Q, 0.30 Q and 200 Q respectively. Calculate the
induced e.m.f. and the armature current. Allow 1.0 V per brush for
contact drop.
Home work2: A 4-pole, long-shunt lap-wound generator supplies 25
kW at a terminal voltage of 500 V. The armature resistance is 0.03 ohm,
series field resistance is 0.04 ohm and shunt field resistance is 200 ohm.
The brush drop may be taken as 1.0 V. Determine the e.m.f. generated.
Calculate also the No. of conductors if the speed is 1200 r.p.m. and flux
per pole is 0.02 weber. Neglect armature reaction.
Expert Solution
![](/static/compass_v2/shared-icons/check-mark.png)
This question has been solved!
Explore an expertly crafted, step-by-step solution for a thorough understanding of key concepts.
This is a popular solution!
Trending now
This is a popular solution!
Step by step
Solved in 3 steps with 2 images
![Blurred answer](/static/compass_v2/solution-images/blurred-answer.jpg)
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Recommended textbooks for you
![Power System Analysis and Design (MindTap Course …](https://www.bartleby.com/isbn_cover_images/9781305632134/9781305632134_smallCoverImage.gif)
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning
![Power System Analysis and Design (MindTap Course …](https://www.bartleby.com/isbn_cover_images/9781305632134/9781305632134_smallCoverImage.gif)
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning