A three-phase transposed line is composed of one ACSR 159,000 cmil, 54/19 Lapwing conductor per phase with flat horizontal spacing of 8 meters as shown in Figure FE-1. The GMR of each conductor is 1.515 cm. a. Determine the inductance per phase per kilometer of the line. This line is to be replaced by a two-conductor bundle with 8-m spacing mea- sured from the center of the bundles as shown in Figure FE-2. The spacing between the conductors in the bundle is 40 cm. If the line inductance per phase is to be 77 percent of the inductance in part (a), what would be the GMR of each new conductor in the bundle? b. 0,0 D12 = 8 m D23 = 8 m 40 -D12 = 8 m- -D23 = 8 m- - D13 = 16 m- -D13 = 16 m - %3D Figure FE-1 Figure FE-2

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter4: Transmission Line Parameters
Section: Chapter Questions
Problem 4.18P: A 230-kV, 60-Hz, three-phase completely transposed overhead line has one ACSR 954 kcmil conductor...
icon
Related questions
Question
A three-phase transposed line is composed of one ACSR 159,000 cmil, 54/19
Lapwing conductor per phase with flat horizontal spacing of 8 meters as shown
in Figure FE-1. The GMR of each conductor is 1.515 cm.
a.
Determine the inductance per phase per kilometer of the line.
b.
This line is to be replaced by a two-conductor bundle with 8-m spacing
mea- sured from the center of the bundles as shown in Figure FE-2. The
spacing between the conductors in the bundle is 40 cm. If the line
inductance per phase is to be 77 percent of the inductance in part (a),
what would be the GMR of each new conductor in the bundle?
a
b
0,0
D12 = 8 m
D23 = 8 m
- 40
-D12 = 8 m-
-D23 = 8 m-
- D13 = 16 m-
D13 = 16 m-
%3D
Figure FE-1
Figure FE-2
Transcribed Image Text:A three-phase transposed line is composed of one ACSR 159,000 cmil, 54/19 Lapwing conductor per phase with flat horizontal spacing of 8 meters as shown in Figure FE-1. The GMR of each conductor is 1.515 cm. a. Determine the inductance per phase per kilometer of the line. b. This line is to be replaced by a two-conductor bundle with 8-m spacing mea- sured from the center of the bundles as shown in Figure FE-2. The spacing between the conductors in the bundle is 40 cm. If the line inductance per phase is to be 77 percent of the inductance in part (a), what would be the GMR of each new conductor in the bundle? a b 0,0 D12 = 8 m D23 = 8 m - 40 -D12 = 8 m- -D23 = 8 m- - D13 = 16 m- D13 = 16 m- %3D Figure FE-1 Figure FE-2
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
Transmission Line Parameter and Scattering Parameter (S-parameter)
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning