A three-phase 480-V 1200-kVA synchronous generator supplies rated load at a lagging power factor of 75 percent. If the efficiency of the generator is 90 percent, what horsepower is the prime mover delivering to the generator?

Delmar's Standard Textbook Of Electricity
7th Edition
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Stephen L. Herman
Chapter7: Parallel Circuits
Section: Chapter Questions
Problem 4PP: Using the rules for parallel circuits and Ohmslaw, solve for the missing values....
icon
Related questions
Question

8-

L2 L3
LI
Orees
alwo
oreeo
aus
ous
reed.
Figure 8
arus
awo
oreeo
Transcribed Image Text:L2 L3 LI Orees alwo oreeo aus ous reed. Figure 8 arus awo oreeo
B) 80 percent power factor?
a) 487.5 kW
- b) 780 kW
c) 975 kW
d) none of the above
C) 50 percent power factor?
a) 487.5 kW
b) 780 kW
c) 975 kW
d) none of the above
D-F.
If the voltage rating is 2400 V, what is the current rating at each power factor?
D) unity power factor
a) 234.55 A
b) 325 A
c) 406.25 A
d) none of the above
E) 80 percent power factor
a) 234.55 A
b) 325 A
c) 406.25 A
d) none of the above
F) 50 percent power factor
a) 234.55 A
b) 325 A
c) 406.25 A
d) none of the above
A three-phase 480-V 1200-kVA synchronous generator supplies rated load at a lagging power
factor of 75 percent. If the efficiency of the generator is 90 percent, what horsepower is the prime
mover delivering to the generator?
8.
a) 1201 hp
b) 1340 hp
c) 1787 hp
d) none of the above
Transcribed Image Text:B) 80 percent power factor? a) 487.5 kW - b) 780 kW c) 975 kW d) none of the above C) 50 percent power factor? a) 487.5 kW b) 780 kW c) 975 kW d) none of the above D-F. If the voltage rating is 2400 V, what is the current rating at each power factor? D) unity power factor a) 234.55 A b) 325 A c) 406.25 A d) none of the above E) 80 percent power factor a) 234.55 A b) 325 A c) 406.25 A d) none of the above F) 50 percent power factor a) 234.55 A b) 325 A c) 406.25 A d) none of the above A three-phase 480-V 1200-kVA synchronous generator supplies rated load at a lagging power factor of 75 percent. If the efficiency of the generator is 90 percent, what horsepower is the prime mover delivering to the generator? 8. a) 1201 hp b) 1340 hp c) 1787 hp d) none of the above
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps with 1 images

Blurred answer
Knowledge Booster
KVL and KCL
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Recommended textbooks for you
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning
Electricity for Refrigeration, Heating, and Air C…
Electricity for Refrigeration, Heating, and Air C…
Mechanical Engineering
ISBN:
9781337399128
Author:
Russell E. Smith
Publisher:
Cengage Learning