A 30 hp, three-phase, wye connected, 60 Hz, 360 VLL, synchronous motor is operating at 50% full load, rated voltage and 0.8 pf leading (over-excited). The motor has negligible armature resistance and a synchronous reactance of 2.5 02/phase. Stator core loss is 1kW and friction and windage loss is 1.5 kW. a. Calculate the new value of line-to-neutral excitation voltage and load angle when the field current is adjusted for 0.85 pf lagging with the same 15 hp load. Determine the load angle, current (with angle), and the reactive power exported (positive) or imported (negative), when the motor load is 30 hp and the line-to-neutral excitation voltage is 255V. b.

Delmar's Standard Textbook Of Electricity
7th Edition
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Stephen L. Herman
Chapter32: Three-phase Motors
Section: Chapter Questions
Problem 6RQ: Name three factors that determine the torque produced by an induction motor.
icon
Related questions
Question
2
Helting. Avoid interruption and keep your files safe with genuine Office today.
b.
3
5
A 30 hp, three-phase, wye connected, 60 Hz, 360 VLL, synchronous motor is operating at 50% full load,
rated voltage and 0.8 pf leading (over-excited). The motor has negligible armature resistance and a
synchronous reactance of 2.5 02/phase. Stator core loss is 1kW and friction and windage loss is 1.5 kW.
a. Calculate the new value of line-to-neutral excitation voltage and load angle when the field
current is adjusted for 0.85 pf lagging with the same 15 hp load.
Determine the load angle, current (with angle), and the reactive power exported (positive) or
imported (negative), when the motor load is 30 hp and the line-to-neutral excitation voltage is
255V.
Get genu
7
Transcribed Image Text:2 Helting. Avoid interruption and keep your files safe with genuine Office today. b. 3 5 A 30 hp, three-phase, wye connected, 60 Hz, 360 VLL, synchronous motor is operating at 50% full load, rated voltage and 0.8 pf leading (over-excited). The motor has negligible armature resistance and a synchronous reactance of 2.5 02/phase. Stator core loss is 1kW and friction and windage loss is 1.5 kW. a. Calculate the new value of line-to-neutral excitation voltage and load angle when the field current is adjusted for 0.85 pf lagging with the same 15 hp load. Determine the load angle, current (with angle), and the reactive power exported (positive) or imported (negative), when the motor load is 30 hp and the line-to-neutral excitation voltage is 255V. Get genu 7
Expert Solution
steps

Step by step

Solved in 4 steps with 1 images

Blurred answer
Knowledge Booster
Stator and Rotor Magnetic Field
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning