4. Two balanced loads are connected in parallel to a three-phase, 460-V source. Load A is 900 kVA at a power factor of 0.6 lagging, and load B is 400 kW at a power factor of 0.8 leading. Calculate (a) total kW and kVAr, (b) overall power factor and (c) line currents.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.22P: A balanced Y-connected voltage source with Eag=2770volts is applied to a balanced-Y load in parallel...
icon
Related questions
icon
Concept explainers
Question
4. Two balanced loads are connected in parallel to a three-phase, 460-V source.
Load A is 900 kVA at a power factor of 0.6 lagging, and load B is 400 kW at a
power factor of 0.8 leading. Calculate (a) total kW and kVAr, (b) overall power
factor and (c) line currents.
Transcribed Image Text:4. Two balanced loads are connected in parallel to a three-phase, 460-V source. Load A is 900 kVA at a power factor of 0.6 lagging, and load B is 400 kW at a power factor of 0.8 leading. Calculate (a) total kW and kVAr, (b) overall power factor and (c) line currents.
Expert Solution
steps

Step by step

Solved in 5 steps with 5 images

Blurred answer
Knowledge Booster
Measuring instrument
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning