4. A three-phase, 7.5Hp, 230V, 60Hz, Delta connected induction motor was tested and give the following input data: No load Test: I = 10A P = 650W slip = 0.8333% Load Test: I = 19A, P = 6800W slip = 3% Resistance test between two stator terminals: Vdc = 9V , Idc = 20A  Assume K = 1.5 Determine the efficiency of the motor during the load test

Delmar's Standard Textbook Of Electricity
7th Edition
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Stephen L. Herman
Chapter32: Three-phase Motors
Section: Chapter Questions
Problem 6RQ: Name three factors that determine the torque produced by an induction motor.
icon
Related questions
Question

4. A three-phase, 7.5Hp, 230V, 60Hz, Delta connected induction motor was tested and give the following input data:
No load Test: I = 10A P = 650W slip = 0.8333%
Load Test: I = 19A, P = 6800W slip = 3%
Resistance test between two stator terminals: Vdc = 9V , Idc = 20A 
Assume K = 1.5
Determine the efficiency of the motor during the load test