A building has a calculated cooling load of 410 kW. The latent portion of the load is 100 kW. The space is to be maintained at 25 C DBT and 50% RH. Outdoor air at 38 c and 50% RH, and 10% by mass of the air supplied to the space is outdoor air. Air is to be supplied to the space at not less than 18 c. Find:: " a- The minimum amount of air supplied to the space in m³\s, b- The volume flow rates of the return air, exhaust air, and outdoor air, c- The conditions and volume flow rates of the air entering the cooling coil, d- The capacity, apparatus dew point temperature, and by pass factor of the cooling EY S 17 coil..

Principles of Heat Transfer (Activate Learning with these NEW titles from Engineering!)
8th Edition
ISBN:9781305387102
Author:Kreith, Frank; Manglik, Raj M.
Publisher:Kreith, Frank; Manglik, Raj M.
Chapter6: Forced Convection Over Exterior Surfaces
Section: Chapter Questions
Problem 6.8P
icon
Related questions
Question
A building has a calculated cooling load of 410 kW. The latent portion of the load is
100 kW. The space is to be maintained at 25 C DBT and 50% RH. Outdoor air at 38 c and
50% RH, and 10% by mass of the air supplied to the space is outdoor air. Air is to be
supplied to the space at not less than 18 c. Find::
S
a- The minimum amount of air supplied to the space in m³\s,
b- The volume flow rates of the return air, exhaust air, and outdoor air,
c- The conditions and volume flow rates of the air entering the cooling coil,
d- The capacity, apparatus dew point temperature, and by pass factor of the cooling
coil.
Transcribed Image Text:A building has a calculated cooling load of 410 kW. The latent portion of the load is 100 kW. The space is to be maintained at 25 C DBT and 50% RH. Outdoor air at 38 c and 50% RH, and 10% by mass of the air supplied to the space is outdoor air. Air is to be supplied to the space at not less than 18 c. Find:: S a- The minimum amount of air supplied to the space in m³\s, b- The volume flow rates of the return air, exhaust air, and outdoor air, c- The conditions and volume flow rates of the air entering the cooling coil, d- The capacity, apparatus dew point temperature, and by pass factor of the cooling coil.
Expert Solution
steps

Step by step

Solved in 4 steps with 4 images

Blurred answer
Knowledge Booster
Work and Heat
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Principles of Heat Transfer (Activate Learning wi…
Principles of Heat Transfer (Activate Learning wi…
Mechanical Engineering
ISBN:
9781305387102
Author:
Kreith, Frank; Manglik, Raj M.
Publisher:
Cengage Learning